Brief Description: School District of Solon Springs
Resolution for Revenue Limit Exemption for Energy Efficiencies
At this the Regular Meeting of the Board of Education on Monday, October 19, 2009, be it resolved that the School District of Solon Springs is exercising its taxing authority under s. 121.91 (4) (o), Wis. Stats. to exceed the revenue limit on a non-recurring basis by an amount the district will spend on new energy efficiency measures for the 2009-10 school year. The amount to be levied and expended is $32,821.
The board has identified the following required performance indicators (supplied by Focus on Energy consultants) that will measure the energy savings and/or energy cost avoidance in an amount equal to the exemption request and will include a timeline:
The district proposes to remove four separate freezer units and two cooler units two of which date to 1960 and replace these seven units with one walk in freezer and one walk in cooler unit. A study conducted by Focus on Energy lists the performance indicators for this project as:
Equipment being removed annual kW source*
Walk in freezer Copeland KATB 010A-CAV 15555 table 4-41
Reach-in Freezer Manitowoc Koolaid KF3 14400 table 4-18
Reach-in Freezer Norlake C-cf2SSD-002 9800 table 4-18
Reach-in Freezer Norlake NF-255 9800 table 4-18
Chest Freezer Sears Model 253 357 energy guide
Walk-in Cooler Copeland KAMB-007E-CAV 16200 table 4-39
Reach in cooler Norlake GR422wuw-o 4300 table 4-24
ANNUAL kWh 70412
Peak kw 8.0379
*Arthur D. Little Energy Savings Potential for Commercial Refrig. Equip.
Replacement Equipment
Annual kW
Walk-in freezer MOHO14L63
200 volts 6.3 amps 15,276
Defrost heater 2364
EC motor on evap fan (2) 2067
Walk-in cooler MOHO10X63 10591
Compressor fan 12,379
EC motor on evap. Fan 1034
ANNUAL kWh 43711
Peak kw 2.95
Annual Savings
Peak Savings 5.08 peak kW
Kilowatt annual Savings 26701
X electric rate .0947
ANNUAL COST SAVINGS 2,528
Payback estimate 12.27 years
An evaluation of the energy performance indicators will be included as an addendum in the required 2010-2011 published budget summary document per s. 65.90, Wis. Stats., and in the school district’s newsletter.
Motion by _Gitzy Wicklund__________________________, Seconded by ____Lucy Linsmeyer____________________ on a vote of ____3__ aye, ____0____nay. This resolution was approved at the regular meeting of the Board of Education, School District of Solon Springs on October 19, 2009.
Gitzy Wicklund , Clerk
School District of Solon Springs
Actual Wording: The School District of Solon Springs exercised its taxing authority to exceed the revenue limit on a non- recurring basis by $32821.00 on energy efficiency measures and renewable energy products for the 2009-2010 school year. The district has expended $32821.00 of this revenue limit authority. As a result of these expenditures, the district has met the following performance indicators:
The district removed 7 freezer/cooler units and replaced them with one walk-in freezer unit and one walk-in cooler unit. The project was completed during the 2009/2010 school year. Wisconsin Focus on Energy prepared the energy savings report. There is a savings of 26,701 kilowatts annually. At the current electric rate of .0947, the annual savings is $2528.00. This project has an estimated payback time of 12.27 years based upon current energy costs.
|
| |
| |
| |